From: TonyS on
D Yuniskis wrote:
> Sylvia Else wrote:
>
> Grounding the mains to "plumbing" *was* common in the US many
> years ago. Now, I believe, you *must* ground to a metal
> rod driven into the earth (8 ft?). Note that if the water
> meter was removed, your earth-through-plumbing would fail.
>
>
> This is how GFCI breakers work -- they watch for current "leaking"
> off to ground someplace other than in the "return" conductor.

In this case the GFCI (or RCD in AU) will not trip as the current through the
load is the same going in and out. I have RCDs on all 3 phases and none of them
tripped.

Tony
From: bob urz on
Phil Allison wrote:
> "Stupider than Anyone Else"
>
>> I have to phases of power supply to my house - so three power lines, two
>> phases plus neutral.
>>
>> I've on occasion wondered what would happen if we lost the neutral line.
>> It seems to me that we'd then have the voltage between the two phases
>> across two sets of appliances, one set attached to one phase, and the
>> other set attached to the other phase, with the two sets in series as a
>> result of their common connection to the neutral wire. Since the two sets
>> are unlikely to represent equal loads, the net result would be a large
>> overvoltage on one set of appliances.
>>
>> My electrician says it's not an issue, but I can't see why.
>
>
> ** Loss of the neutral conductor in a 3 phase ( or 2 phase) AC supply system
> can easily be a DISASTROUS event.
>
> For example:
>
> In the live entertainment productions - high powered lighting and sound
> systems operate from 3 phase outlets via a hefty 5 pin plug and socket. If,
> due to wear and tear or damage to the plug or socket, one of the phases
> drops out - that is an annoyance but not a disaster.
>
> However, if the pin carrying the neutral fails to connect or as is often the
> case *disconnects* during a show because of overheating - ALL HELL
> BREAKS LOOSE !!
>
> Typically, some of the lamps will glow very brightly for a second or two and
> fail, then other previously dim lamps will follow suit. The AC fuses in
> amplifiers will pop instantly and some equipment will be seriously damaged
> when the PSU sections are destroyed. It all happens in a few seconds, while
> the operators stand there with their mouths open !!!
>
>
>
>
> .... Phil
>
>
>
>
I recently had such an event happen at a theater. It was county fair
season and the vendor was scrapping the bottom of the barrel for gear.
It was an old distro, with a Yamaha 3500 FOH, with an effects racks.

About 2 hours before house, everything was working when i heard the
system crackling. I looked over at FOH and the lights were flashing.
Then smoke started coming out of the effects rack. I ran to the stage
to shut off power amps and shut everything down.

It was split phase going to FOH. Measured 220 between the hots, and
nothing to neutral. Somewhere, the neutral was lost. Checked the
connector on stage and changed the plugged slot on the distro.

At that point, power came back the way it should. BUT, the effects rack
was still smoking due to fried MOV's in the Furman plug strip.
And all the Drawmer compressors were DOA. luckily, the Yamaha console
was ok. Did the show with a few less toys.

bob
From: Dave Platt on

In article <0083b31e$0$1587$c3e8da3(a)news.astraweb.com>,
Sylvia Else <sylvia(a)not.at.this.address> wrote:

>I have to phases of power supply to my house - so three power lines, two
>phases plus neutral.
>
>I've on occasion wondered what would happen if we lost the neutral line.
>It seems to me that we'd then have the voltage between the two phases
>across two sets of appliances, one set attached to one phase, and the
>other set attached to the other phase, with the two sets in series as a
>result of their common connection to the neutral wire. Since the two
>sets are unlikely to represent equal loads, the net result would be a
>large overvoltage on one set of appliances.
>
>My electrician says it's not an issue, but I can't see why.

It's a huge issue.

It has happened twice, at my house. In both cases, a squirrel had
chewed through the neutral wire (they apparently like to sharpen /
exercise their teeth on the rubbery insulation).

The symptoms were much as you suggest. Voltage goes wonky, with the
voltage being fed to each phase being dependent on the various loads
connected to both phases. Voltages at the high-amperage appliances
can drop (and this can result in burned-out motors) while voltages on
the opposite phase can spike upwards (burning out incandescent lights,
damaging other appliances through over-voltage). Worst case would be
a heavy load on one phase, and only very light loads on the other
phase... the lightly loaded side could jump up to almost double
voltage.

The oddest symptom we noticed was that when a heavy load switched on
(e.g. refrigerator or microwave), room lights would suddenly
brighten... just the opposite of what would normally occur.

Both times this happened, we noticed the weirdness immediately, called
the electric company (PG&E), and they dispatched a service team on a
priority basis.

The dispatcher told me that they consider *any* sort of "high voltage,
low voltage" trouble report to justify an urgent response. She had
understood my use of the phrase "open neutral", and I infer that this
is a not-terribly-unusual situation for them.

After the second time this happened, the PG&E guys decided that our
existing pole-drop was not repairable (it had already been spliced at
least one). They installed a newer, higher-amperage-rated drop (which
might even have had some armoring). The problem hasn't recurred...
I'm keeping my fingers crossed.

--
Dave Platt <dplatt(a)radagast.org> AE6EO
Friends of Jade Warrior home page: http://www.radagast.org/jade-warrior
I do _not_ wish to receive unsolicited commercial email, and I will
boycott any company which has the gall to send me such ads!
From: Jamie on
D Yuniskis wrote:

> Sylvia Else wrote:
>
>> Phil Allison wrote:
>>
>>> The MEN system:
>>>
>>> In Australia, AC power delivery uses a system called " Multiple Earth
>>> Neutral " - which requires that the neutral conductors in a
>>> premises be connected to the plumbing system at the distribution
>>> board (ie power box). It also requires that an earth stake be
>>> installed for the same purpose, but some older premises may not have
>>> this.
>>
>>
>> If as you say, neutral has to be tied to Earth at the premises, then I
>> can indeed see that the situation might not be so bad.
>
>
> Grounding the mains to "plumbing" *was* common in the US many
> years ago. Now, I believe, you *must* ground to a metal
> rod driven into the earth (8 ft?). Note that if the water
> meter was removed, your earth-through-plumbing would fail.
>
>> On the face of it, having significant current flowing from neutral to
>> Earth would have to indicate a fault. It would be nice for the
>> breakers to trip in such a situation, but I can't see that they will.
>
>
> This is how GFCI breakers work -- they watch for current "leaking"
> off to ground someplace other than in the "return" conductor.

Please don't go there, there are many experts that really don't know
how a GFCI is suppose to work.

They thieve on the idea that most units now sold have the arc
detection in them and no longer label arc (AGFCI) detection as part of
the unit,which does not require a ground path, along with it having the
original ground fault system which does require grd path to fault.

Those that have installed these units in outlets that have no ground
in them, there by, allowing the unaware person to become the ground for
it. They think it's ok because just sliding the plug in/out, which
causes those nice little arc's to form, from the appliance load, will
trip it.

And it's obvious, if you don't have a working ground from the
receptacle to the appliance, the GFCI isn't going to work very well when
the appliance starts generating small little intermitting shorts that
would normally trip the device if the ground on the appliance was
present to unbalance the common mode device in the GFCI, with out taking
out a human in the process.

Devices like lamp cords, that normally do not have a grd terminal, are
excepted because, the arc detection will actually trip, some times. They
have to be rather large ones before they work, and other times, things
like high powered radio's going by, will false trip them.. That's what
you get for trying to accommodate those that don't want to do it
correctly. This problem is also prevalent in AF-breakers and code allows
variance to accommodate for life saving equipment and the like.

I just love it when the building inspectors use their U-ground testers
on GFCI's that have no working ground at the receptacle to find it not
tripping when they hit that GF test. It brings a smile to my face..

Have a good day..


From: Phil Allison on

"Dave Platt"
> Sylvia Else
>
>>I have to phases of power supply to my house - so three power lines, two
>>phases plus neutral.
>>
>>I've on occasion wondered what would happen if we lost the neutral line.
>>It seems to me that we'd then have the voltage between the two phases
>>across two sets of appliances, one set attached to one phase, and the
>>other set attached to the other phase, with the two sets in series as a
>>result of their common connection to the neutral wire. Since the two
>>sets are unlikely to represent equal loads, the net result would be a
>>large overvoltage on one set of appliances.
>>
>>My electrician says it's not an issue, but I can't see why.
>
> It's a huge issue.


** Sylvia lives in Sydney, Australia and is a MASSIVE TROLL.

Nuts of her the post such a COUNTRY SPECIFIC message to a US newsgroup.




...... Phil