From: Jerry Peters on
D Yuniskis <not.going.to.be(a)seen.com> wrote:
> Sylvia Else wrote:
>> Phil Allison wrote:
>>> The MEN system:
>>>
>>> In Australia, AC power delivery uses a system called " Multiple Earth
>>> Neutral " - which requires that the neutral conductors in a premises
>>> be connected to the plumbing system at the distribution board (ie
>>> power box). It also requires that an earth stake be installed for the
>>> same purpose, but some older premises may not have this.
>>
>> If as you say, neutral has to be tied to Earth at the premises, then I
>> can indeed see that the situation might not be so bad.
>
> Grounding the mains to "plumbing" *was* common in the US many
> years ago. Now, I believe, you *must* ground to a metal
> rod driven into the earth (8 ft?). Note that if the water
> meter was removed, your earth-through-plumbing would fail.

You're *supposed* to have a bypass around the meter for just this
reason, or the ground connected before the meter.

Jerry
>
>> On the face of it, having significant current flowing from neutral to
>> Earth would have to indicate a fault. It would be nice for the breakers
>> to trip in such a situation, but I can't see that they will.
>
> This is how GFCI breakers work -- they watch for current "leaking"
> off to ground someplace other than in the "return" conductor.
From: D Yuniskis on
Jerry Peters wrote:
> D Yuniskis <not.going.to.be(a)seen.com> wrote:
>> Sylvia Else wrote:
>>> Phil Allison wrote:
>>>> The MEN system:
>>>>
>>>> In Australia, AC power delivery uses a system called " Multiple Earth
>>>> Neutral " - which requires that the neutral conductors in a premises
>>>> be connected to the plumbing system at the distribution board (ie
>>>> power box). It also requires that an earth stake be installed for the
>>>> same purpose, but some older premises may not have this.
>>> If as you say, neutral has to be tied to Earth at the premises, then I
>>> can indeed see that the situation might not be so bad.
>> Grounding the mains to "plumbing" *was* common in the US many
>> years ago. Now, I believe, you *must* ground to a metal
>> rod driven into the earth (8 ft?). Note that if the water
>> meter was removed, your earth-through-plumbing would fail.
>
> You're *supposed* to have a bypass around the meter for just this
> reason, or the ground connected before the meter.

I haven't checked a *current* CodeBook but I think connections
to water pipes have to be within a few feet of the pipe's entry
to the building, etc. And the water pipe must have a certain
length *in* the soil, etc.

Buildings with metal structural members often have the building
itself earthed. And, of course, rules change depending on the
potential available on each conductor, etc.

But, as I said, I think this is all deprecated as you can't
*count* on having metal pipes to the water main, etc.
From: Baron on
Phil Allison wrote:

>
> "kreed"
>
>> From what I can gather, pretty much every home in the US has a 120v -
>> 0 - 120v system where the 2x 120v's are 180 degrees out of phase.
>> Between the 2 phases 240v is available for stoves, air conditioners
>> etc.
>>
>> In Australia, most separate homes have a straight single phase 240v
>> supply, its not common for there to be 2,3 separate phases to the
>> average house. Therefore the scenario Sylvia mentions is less likely
>> to occur, as not many people have this multi phase system.
>>
>> The exception here could be blocks of flats, if the main neutral to
>> the building fails, and there isn't a good earth, the imbalance could
>> be a risk.
>
>
> ** There is always a good "earth" available - courtesy of the water
> mains in the street being linked to neutral at every premises.
>
>
> ..... Phil

Except where plastic is in use. Mine is all plastic and the safety
earth is linked to the armouring on the incoming mains feed cable.

--
Best Regards:
Baron.
From: Baron on
Meat Plow wrote:

> On Tue, 24 Nov 2009 11:10:26 +1100, Sylvia Else
> <sylvia(a)not.at.this.address>wrote:
>
>>I have to phases of power supply to my house - so three power lines,
>>two phases plus neutral.
>>
>>I've on occasion wondered what would happen if we lost the neutral
>>line. It seems to me that we'd then have the voltage between the two
>>phases across two sets of appliances, one set attached to one phase,
>>and the other set attached to the other phase, with the two sets in
>>series as a result of their common connection to the neutral wire.
>>Since the two sets are unlikely to represent equal loads, the net
>>result would be a large overvoltage on one set of appliances.
>>
>>My electrician says it's not an issue, but I can't see why.
>>
>>Any thoughts?
>>
>>Sylvia.
>
> Removing the return leg isn't going to cause problems in a properly
> wired US home. Don't know about the UK.

The lights would go out ! Domestic properties usually have just a 240v
single phase feed. Usually you would get a single phase running down
one side of the street and another phase running down the other.

--
Best Regards:
Baron.
From: whit3rd on
On Nov 23, 5:38 pm, D Yuniskis <not.going.to...(a)seen.com> wrote:

> Grounding the mains to "plumbing" *was* common in the US many
> years ago.  Now, I believe, you *must* ground to a metal
> rod driven into the earth (8 ft?).

Just to be clear, my copy of the US National Electric Code clearly
requires (section 250-80) plumbing to be bonded to the electrical
service
ground, it just doesn't allow the buried water piping to substitute
for
a ground rod or similar to-the-soil connection.

The ground wire from the interior water pipe grounds the pipes, not
the
electric wiring.